Online Analyzer

Online Residual Chlorine/Total Chlorine Analyzer

Model: :ATH13

The ULT200 ultrasonic level transmitter provides reliable non-contact level measurement for liquids, solids and slurries. With advanced echo processing technology, it delivers high accuracy even in challenging industrial environments.

  • 24-Hour Response Fast turnaround time
Get a Quote


Product Model


ATH10


ATH13


Measurement Range


0.20-500ppm CaCO3(Refer to reagent type)


0.00-5.00mg/l(ppm)


Power Supply


24VDC, 25W(220VAC power adapter optional)


110-240VAC, 50/60Hz


Output

Current Output: 0/4-20 mA, Max. 750 Ω

Relay Output: 2x isolated relay outputs (NO/NC), 30 VDC 1A

Output:0/4-20mA, Max. 750Ω

;RS485 Modbus RTU


Measurement

Principle


Titration colorimetry


DPD colorimetry


Measurement

Accuracy

Measurement Accuracy: ±5% of selected reagent upper limit Repeatability: ±5% of selected reagent upper limit


±1%f.s.


Cleaning Method


Manual cleaning


Alarm Point


-

2 independent sets of Hi/Lo alarm points with hysteresis setting,

5A/250VAC.

Sample

Pressure/Flow Rate

Clear, free of suspended solids and bubbles

pH: 4-10.5; Fe: <3 ppm; Cu: <0.2 ppm;Al: <0.1 ppm; Mn: <0.2 ppm


Flow Rate: 1L/min


Sample Temperature


5-40℃

Temperature:  0-50°C

Humidity:   10-95% RH, non-condensing


Pressure Range


0.5-5 bar, recommended 1-2 bar


1bar

Dimensions &

Weight


250 x 360 x 110 mm, approx. 2.5 kg (with housing)


Wall-mounted  300×400×180mm


Protection Rating


IP54


IP65

Message
Contact number

+86 18961557757

+86 18018362100

Back to top